Eaton 9PX 8kVA 1:1 Power Module , ( no internal batteries, add 1 x 9PXEBM240 minimum to make UPS) , no rail kits
Eaton 9PX 8kVA 1:1 Power Module , ( no internal batteries, add 1 x 9PXEBM240 minimum to make UPS) , no rail kits
- Brand: Eaton
- MPN: 9PX8KIPM
- Part #: UPSPWR62682
- UPC: 743172039361
Specifications
Reviews
Delivery & Pick-up
Returns & Warranty
Related Promotions
Popular UPS & PDU Devices





Eaton 9PX 8kVA 1:1 Power Module , ( no internal batteries, add 1 x 9PXEBM240 minimum to make UPS) , no rail kits
- Brand: Eaton
- MPN: 9PX8KIPM
- Part #: UPSPWR62682
- UPC:743172039361

Product URL: https://www.pbtech.co.nz/product/UPSPWR62682/Eaton-9PX-8kVA-11-Power-Module---no-internal-batte
Branch | New Stock | On Display |
---|---|---|
Albany | 0 | |
Glenfield | 0 | |
Queen Street | 0 | |
Auckland Uni | 0 | |
Penrose | 0 | |
Henderson (Express) | 0 | |
St Lukes | 0 | |
Manukau | 0 | |
Hamilton | 0 | |
Tauranga | 0 | |
New Plymouth | 0 | |
Palmerston North | 0 | |
Petone | 0 | |
Wellington | 0 | |
Head Office | 0 | |
Hornby | 0 | |
Christchurch Central | 0 |
Features
Specifications
On-line double conversion with PFC (Power Factor Correction) system
Configuration
Rack/Tower
Part Number
9PX8KiPM and 9PXEBM240
Rating (VA/Watts)
8000/7200
Dimensions (H x W x D, mm)
260 (6U) x 440 x 685
Weight (kg)
84
Warranty
3 years on electronics, 2 years on battery
Electrical Input
Connection
Hardwired - see manual for terminal block layout
Input Voltage Range
176-276V without derating (up to 100-276V with derating)
Nominal Voltage
200/208/220/230/240/250V
Frequency
50/60 Hz autoselection
Frequency Range
40-70 Hz
Short Circuit Current
120 A
THDI
<5%
Electrical Output
Voltages
200/208/220/230/240/250V +/- 1%
Voltage
THD < 2%
Output Receptacles
Hardwired - see manual for terminal block layout
Overload Capacity
102-110% : 120s, 110-125%: 60s, 125-150%: 10s, >150%: 900ms
Efficiency (Normal Mode)
Up to 95% in Online mode, 98% in Hi-Efficiency mode
Output Frequency
50/60 Hz autoselect, frequency converter as standard
Load Crest Factor
3:1
Battery Management
ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units.
Extended Battery Capability
EBM (3U)