Enlogic ENL-EN1337 Input Metered, iPDU, 220-240VAC, 1- phase, (36)C13, (6)C19, 2x 16A HydraulicMagnetic Circuit breakers, 32A input, 3m Lead to IEC 60309 332P6 plug Enlogic-EN2.0 Advantage series - 5yr warranty
Out of stock
Enlogic ENL-EN1337 Input Metered, iPDU, 220-240VAC, 1- phase, (36)C13, (6)C19, 2x 16A HydraulicMagnetic Circuit breakers, 32A input, 3m Lead to IEC 60309 332P6 plug Enlogic-EN2.0 Advantage series - 5yr warranty
- Brand: Enlogic
- MPN: ENL-EN1337
- Part #: RACEGC1011
- UPC:
- Brand: Enlogic
- MPN: ENL-EN1337
- Part #: RACEGC1011
- UPC:
Features
Specifications
Reviews
Delivery & Pick-up
Returns & Warranty
Popular Racks & Cabinets





Enlogic ENL-EN1337 Input Metered, iPDU, 220-240VAC, 1- phase, (36)C13, (6)C19, 2x 16A HydraulicMagnetic Circuit breakers, 32A input, 3m Lead to IEC 60309 332P6 plug Enlogic-EN2.0 Advantage series - 5yr warranty
- Brand: Enlogic
- MPN: ENL-EN1337
- Part #: RACEGC1011

Product URL: https://www.pbtech.co.nz/product/RACEGC1011/Enlogic-ENL-EN1337-Input-Metered-iPDU-220-240VAC-1
Branch | New Stock | On Display |
---|---|---|
Auckland - Albany | 0 | |
Auckland - Glenfield | 0 | |
Auckland - Queen Street | 0 | |
Auckland - Auckland Uni | 0 | |
Auckland - Newmarket | 0 | |
Auckland - Westgate | 0 | |
Auckland - Penrose | 0 | |
Auckland - Henderson (Express) | 0 | |
Auckland - St Lukes | 0 | |
Auckland - Manukau | 0 | |
Hamilton | 0 | |
Tauranga | 0 | |
New Plymouth | 0 | |
Palmerston North | 0 | |
Petone | 0 | |
Wellington | 0 | |
Auckland - Head Office | 0 | |
Auckland - East Tamaki Warehouse | 0 | |
Christchurch - Hornby | 0 | |
Christchurch - Christchurch Central | 0 | |
Dunedin | 0 |
Features
Enlogic intelligent PDUs are a range of premium intelligent Power Distribution Units. Available in single or 3-Phase formats with options of overall PDU power monitoring, individual outlet monitoring or outlet switching. Enlogic PDUs have a host of advanced features including bill-grade metering, advanced networking including IP cascading of up to 64 PDUs, colour coded circuit breakers, environmental monitoring and access control, and a tool-less hot-swap Network Management Card for maximum availability and future upgrades.
Specifications
PDU Function
Metering Attributes
Voltage(V), Current(A), Apparent Power(kVA), Real Power(kW), Power Factor, Energy (kWh)
Metering Accuracy
± 1% to ISO/IEC 62052-21
Metering Locations
Input phase and circuit breaker level measurements
Remote Outlet Switching
No
Electrical Input
Input Plug Type
IEC 60309 332P6
Acceptable input voltage
200-240VAC, 1ph
Input current (phase)
32A
Input frequency
50/60 Hz
Max Input power
7.68 kVA @ 240 VAC
Electrical Output
Output voltage
230 V
Maximum output current (phase)
32A
Overload protection (internal)
(2) 1-pole, 16A hydraulic-magnetic circuit breakers
Outlet configuration
(36)C13, (6)C19
Physical
Chassis Dimensions (L x W x D) in
68.9 x 2.05 x 2.09
Depth at circuit breaker, in
2.087
Input cord length
10'
Environmental
Operating Temperature
-5 to 60°C (23 to 140°F)
Storage Temperature
-20 to 60°C (-4 to 140°F)
Humidity (operating/storage)
5-90% RH / 5-95% RH; non-condensing
Max operating elevation, above MSL
3,000 m (9,840 ft)
Compliance
Safety & Environmental