Enlogic ENL-EN2329 Enlogic 2.0 Input Metered, Outlet Switched, iPDU, 220-240VAC, 1- phase,(24)C13, (8)C19, (2)16A hydraulic-magnetic CBs, 32A input, IEC 60309 332P6 plug
Out of stock
Enlogic ENL-EN2329 Enlogic 2.0 Input Metered, Outlet Switched, iPDU, 220-240VAC, 1- phase,(24)C13, (8)C19, (2)16A hydraulic-magnetic CBs, 32A input, IEC 60309 332P6 plug
- Brand: Enlogic
- MPN: ENL-EN2329
- Part #: RACEGC1015
- UPC:
- Brand: Enlogic
- MPN: ENL-EN2329
- Part #: RACEGC1015
- UPC:
Features
Specifications
Reviews
Delivery & Pick-up
Returns & Warranty
Popular Racks & Cabinets





Enlogic ENL-EN2329 Enlogic 2.0 Input Metered, Outlet Switched, iPDU, 220-240VAC, 1- phase,(24)C13, (8)C19, (2)16A hydraulic-magnetic CBs, 32A input, IEC 60309 332P6 plug
- Brand: Enlogic
- MPN: ENL-EN2329
- Part #: RACEGC1015

Product URL: https://www.pbtech.co.nz/product/RACEGC1015/Enlogic-ENL-EN2329-Enlogic-20-Input-Metered-Outlet
Branch | New Stock | On Display |
---|---|---|
Auckland - Albany | 0 | |
Auckland - Glenfield | 0 | |
Auckland - Queen Street | 0 | |
Auckland - Auckland Uni | 0 | |
Auckland - Newmarket | 0 | |
Auckland - Westgate | 0 | |
Auckland - Penrose | 0 | |
Auckland - Henderson (Express) | 0 | |
Auckland - St Lukes | 0 | |
Auckland - Manukau | 0 | |
Hamilton | 0 | |
Tauranga | 0 | |
New Plymouth | 0 | |
Palmerston North | 0 | |
Petone | 0 | |
Wellington | 0 | |
Auckland - Head Office | 0 | |
Auckland - East Tamaki Warehouse | 0 | |
Christchurch - Hornby | 0 | |
Christchurch - Christchurch Central | 0 | |
Dunedin | 0 |
Features
The EN2329 Input Metered, Outlet Switched PDU combines energy metering, power and environmental monitoring with remote outlet on/off switching to monitor, protect, and manage the rack environment. Utility grade metering at the phase input and internal circuit breaker levels provides comprehensive overload monitoring. Outlet power-up sequencing protects against inrush current overload and allows users to define equipment boot-up order and timing. While remote on/off control allows authorized users to power-cycle remote equipment and implement rack-level power access controls to power on/off each outlet. Advanced network management features allow for remote access and integration with accessories including environmental monitoring and security access solutions.
Specifications
PDU Function
Metering Attributes
Voltage(V), Current(A), Apparent Power(kVA), Real Power(kW), Power Factor, Energy (kWh)
Metering Accuracy
± 1% to ISO/IEC 62052-21
Metering Locations
Input phase and circuit breaker measurements
Remote Outlet Switching
Yes
Electrical Input
Input Plug Type
IEC 60309 332P6
Acceptable input voltage
200-240VAC, 1ph
Input current (phase)
32A
Input frequency
50/60 Hz
Max Input power
7.68 kVA @ 240 VAC
Electrical Output
Output voltage
230 V
Maximum output current (phase)
32A
Overload protection (internal)
(2) 1-pole, 16A hydraulic-magnetic circuit breakers
Outlet configuration
(24)C13, (8)C19
Physical
Chassis Dimensions (L x W x D) in
68.9 x 2.05 x 2.09
Depth at circuit breaker, in
2.953
Input cord length
10'
Environmental
Operating Temperature
-5 to 60°C (23 to 140°F)
Storage Temperature
-20 to 60°C (-4 to 140°F)
Humidity (operating/storage)
5-90% RH / 5-95% RH; non-condensing
Max operating elevation, above MSL
3,000 m (9,840 ft)
Compliance
Safety & Environmental
CE, Demko Certified to IEC/EN60950-1, RoHS, REACH