PowerShield Rack/Tower (2RU) Battery bank. Includes 16x 12v.
PowerShield Rack/Tower (2RU) Battery bank. Includes 16x 12v.
- Brand: PowerShield
- MPN: PSRTBB16
- Part #: UPSPSD0031
- UPC:
- Brand: PowerShield
- MPN: PSRTBB16
- Part #: UPSPSD0031
- UPC:
Features
Specifications
Reviews
Delivery & Pick-up
Returns & Warranty
Popular UPS Battery Modules





PowerShield Rack/Tower (2RU) Battery bank. Includes 16x 12v.
- Brand: PowerShield
- MPN: PSRTBB16
- Part #: UPSPSD0031

Product URL: https://www.pbtech.co.nz/product/UPSPSD0031/PowerShield-RackTower-2RU-Battery-bank-Includes-16
Branch | New Stock | On Display |
---|---|---|
Auckland - Albany | 0 | |
Auckland - Glenfield | 0 | |
Auckland - Queen Street | 0 | |
Auckland - Auckland Uni | 0 | |
Auckland - Newmarket | 0 | |
Auckland - Westgate | 0 | |
Auckland - Penrose | 0 | |
Auckland - Henderson (Express) | 0 | |
Auckland - St Lukes | 0 | |
Auckland - Manukau | 0 | |
Hamilton | 0 | |
Tauranga | 0 | |
New Plymouth | 0 | |
Palmerston North | 0 | |
Petone | 0 | |
Wellington | 0 | |
Auckland - Head Office | 0 | |
Auckland - East Tamaki Warehouse | 0 | |
Christchurch - Hornby | 0 | |
Christchurch - Christchurch Central | 0 | |
Dunedin | 0 |
Features
The Centurion RT features true online double conversion. As our highest single phase power density UPS, this sophisticated range will provide the most comprehensive protection for mission critical devices such as sensitive networks, computers, servers, telecom applications, as well as industrial applications.
Meticulously developed by PowerShield engineers to be a world leading technology UPS, the Centurion RT addresses absolutely all requirements and features as has been demanded by the sophisticated Australian power consumer and hence stands in a class of its own, as a world leading UPS technology.
- Exceptional surge protection
- Unity Output power factor (PF=1)
- Informative & easy-shift LCD display
- Rack/Tower design
- Emergency Power Off Function (EPO)
- ECO & advanced ECO mode
- Standard extra large charger
- Hot swappable batteries
Specifications
INPUT
Voltage Range
Line Loss 110~300Vac @ (0~60%) Load; 140~300V @ (60~80%) Load; 176~300Vac @ (80~100%) Load
Low Line Comeback Low Line Loss Voltage + 10V
High Line Comeback High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system; 56Hz ~ 64 Hz @ 60Hz system
Phase
Single phase with ground
Input Power Factor Correction
Less than or Equal to 0.99 @ nominal voltage (100% load)
OUTPUT
Output Voltage
208 / 220 / 230 / 240VAC AC Selectable
AC Voltage Regulation
± 1%
Frequency Range (Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC Mode 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec
Battery Mode 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec
Current Crest Ration
3:1 Max
Harmonic Distortion
Less than or Equal to 1 % @ 100% Linear Load; 4% @ 100% Non-linear Load
Transfer Time
Line to Battery 0 ms
Inverter to Bypass 0 ms
Inverter to Eco < 10 ms
EFFICIENCY
AC Mode
> 94%
Battery Mode
> 93%
BATTERY
Battery Type
Depending on applications
Battery Number
Optional strings of 16 or 20 batteries
Typical Recharge Time
According to external battery pack
Charging Current (max.)
4 A ± 10%
COMMUNICATIONS AND MANAGMENT
Interface
USB and RS232 as standard
Software
PowerShield® NetGuard® software - supports Windows, Linux, Unix and Mac based operating systems
Optional
Intelligent slot for PSSNMPV4, PSModbus or PSAS400 dry contact
OPERATING ENVIRONMENT
Temperature
0 ~ 40°C
Humidity
95% (RH Non-condensing)
Altitude
<1000m